Investigation of ventilation conditions associated with CO2 concentration changes in ultrasonographic exam room from the perspective of COVID-19 infection control

Matsubayashi, R. N.; Harada, S.; Tominaga, M.

2021-03-02 occupational and environmental health
10.1101/2021.03.01.21252598 medRxiv
Show abstract

ObjectivesVentilation is an important factor in preventing COVID-19 infection. To clarify the state of ventilation in ultrasonic exam rooms, as an index of ventilation rate, the carbon dioxide (CO2) concentration in our exam rooms was measured. MethodsWe measured the CO2 concentration in each exam room before the examination and 0-15 minutes after end of the exam. The subjects were 70 cases (abdomen: 24, breast: 16, neck: 16, and musculoskeletal: 14). In infant cases, one parent accompanied the patient during the examination. ResultsThe highest CO2 concentration was 2261 ppm, observed after the breast examination. In all cases, the CO2 concentration in the exam room was highest immediately after the examination or two minutes after. Almost all cases had recovered to within 120% of the pre-examination CO2 concentrations within 15 minutes after the examination. The average CO2 concentration after ultrasonography was significantly higher for breast examinations than others. ConclusionsEven in a hospital with modern ventilation equipment, the CO2 concentration in the ultrasound room was high after the exam and it takes 15 minutes to recover to the pre-exam state. Care must be taken to ensure adequate ventilation in ultrasonographic facilities.

Matching journals

The top 2 journals account for 50% of the predicted probability mass.

50% of probability mass above

"Similar papers" are the closest papers from that journal in the model's embedding space. They show what the match is built on, but the ranking comes mostly from a classifier over the whole training set, not from these examples alone.